The Electrode Steam Boilers in the Collins Walker range have a steam output range of 85 Kg/Hr (ES5) up to a maximum of 6,500 kg/h (ES240). Please note that the maximum output in this instance would require a 690 volt 3–phase electrical supply.
The standard steam output rating of our Electrode Steam Boiler range from a 3 phase 415 volt supply operating from and at 100°C is shown below:
| Model | Steam Output (Kg/Hr) | Load Rating (kW) | Current Per Phase (Amps) |
|---|---|---|---|
| ES5 | 85 | 54 | 75 |
| ES10 | 170 | 108 | 150 |
| ES20 | 340 | 215 | 300 |
| ES40 | 685 | 430 | 600 |
| ES90 | 1370 | 860 | 1200 |
| ES130 | 1980 | 1290 | 1800 |
| ES240 | 3520 | 2300 | 3200 |
3 phase, 4 wire (voltage up to 690V and frequency 50/60Hz to be specified)
Built to BS5500 and independently inspected by Zurich Insurance. Full certification is issued with completed boilers.